Upgrade Procedure
To upgrade the OneView™ software on your ONS-NC600, please carefully follow the upgrade instructions or contact Optigo Networks at support@optigo.net or 1-800-629-6559 for assistance.
To upgrade the OneView™ software on your ONS-NC600, please carefully follow the upgrade instructions or contact Optigo Networks at support@optigo.net or 1-800-629-6559 for assistance.
WARNING
If your OneView system's 'Factory Default Version' is older than 4.2.0-065, please contact Optigo tech support for assistance before you attempt to upgrade your system.
Filename: ons-nc600-fw-4.4.0-169.optg
SHA256 checksum: 9514c279ee3d50232494fd7d243828b90a5a1255e3c3de368fefd7fb9443ab30
New Features & Improvements
New Features & Improvements
- Router management for supported routers.
- Miscellaneous GUI bugs fixed.
- Fixed a bug on Hybrid systems where all of the VLANs on ports configured as 'trunk' would be deleted, except for the lowest one, when the system was restarted or resumed operation after a power outage (e.g. only VLAN 100 would be retained on a trunk port configured with VLANs 100, 200, and 300).
- Fixed bug where the device databases were not being synced on redundant systems.
- Improved report generation performance.
- Fixed bug where duplicate MAC addresses could be entered for IP reservations within the same subnet.
- Fix bug that prevented PoE from being disabled on some ports on ONS-C801pi and ONS-C1601pi edge switches.
Known Issues & Limitations
- Plugging in or unplugging Ethernet cables from an ONS-CU-SFP can result in duplicate link notifications appearing on the Notifications screen.
Workaround: Ignore these - the Edge Switch itself is sending this. - Changing port VLANs occasionally throws an error (Spectra Only).
Workaround: Re-attempt VLAN change. - Some downstream traffic does not pass on VLAN 1 with ONS-C801pi and ONS-C1601pi (Spectra Only).
Workaround: Use a VLAN other than 1. - Notifications on the Windows version of Chrome do not work when using "http".
Workaround: Always use "https" (e.g. https://192.168.10.254). - If data traffic (non-management) can reach the Network Controller, then an excessive amount of broadcast (DoS) may cause performance issues with the GUI (OneView).
Workaround: Use a unique VLAN for management (OneView). - Inter-switch traffic on the same EPON (laser) does not increment traffic counters on bandwidth page (Spectra Only).
- The ONS-C4801p in Hybrid mode can cause issues with the topology view.
New and Updated Documentation
The following is a list of documents that have been updated or newly created to support this release of OneView software:
- Connect OneView™ User Guide
- Router Management with OneView™
- OneView™ Supported Routers
- Router Upgrade with OneView™
- Setting Up Redundancy on Optigo Connect Spectra™ Systems
- Setting Up Redundancy on Optigo Connect Spectra™ Systems with a OneView compatible Router
Comments