IMPORTANT
If you're upgrading from version 4.4.3-188 (or older), please make sure you've purchased the appropriate license(s) for your system. If in doubt, please contact Optigo Networks tech support first.
If you're upgrading from version 4.4.3-188 (or older), please make sure you've purchased the appropriate license(s) for your system. If in doubt, please contact Optigo Networks tech support first.
Upgrade Procedure
To upgrade the OneView™ software on your ONS-NC600, please carefully follow the upgrade instructions or contact Optigo Networks at support@optigo.net.
To upgrade the OneView™ software on your ONS-NC600, please carefully follow the upgrade instructions or contact Optigo Networks at support@optigo.net.
Filename: ons-nc600-fw-4.7.4-335.optg
SHA256 checksum: 76e64ef505d775c6b60cfbf95f2362f5a088ddc22d47552158468795ca5b429a
New Features & Improvements
New Features & Improvements
- Fixed a bug where the RSSI values for the ONS-CR2420GT are all listed as zero.
- Updated the SSL certificate with an expiry date of August 27, 2035.
Known Issues & Limitations
- When using OneClick Secure™ on a redundant system, the settings aren't automatically synced between the systems, even though the GUI indicates that they are.
Workaround: Always manually sync the databases after locking a system down with OneClick Secure™ or unlocking it.
- When using an ONS-CR2420GT switch on a system with a router, Inter-VLAN routing will not work unless the ONS-CR2420T has all of the required VLANs configured on it (e.g. routing from VLAN 123 on the ONS-CR2420GT to VLAN 456 on another switch will only work if VLAN 456 is also on the ONS-CR2420GT).
Workaround: Find an empty port on the ONS-CR2420GT and configure its VLAN mode as 'trunk', with all of the desired VLANs selected.
- In rare cases, bulk assignment of large ranges of VLANs on many trunk ports can result in an ‘HTTP Server Error’ message popup and OneView becoming unresponsive for a few minutes.
Workaround: Close the error message dialog, wait for the system to stabilize, and then, if applicable, re-apply any settings changes that failed to complete.
- Plugging in or unplugging Ethernet cables from an ONS-CU-SFP can result in duplicate link notifications appearing on the Notifications screen.
Workaround: Ignore these - the Edge Switch itself is sending this.
- Changing port VLANs occasionally throws an error (Spectra Only).
Workaround: Re-attempt VLAN change.
- If data traffic (non-management) can reach the Network Controller, then an excessive amount of broadcast (DoS) may cause performance issues with the GUI (OneView).
Workaround: Use a unique VLAN for management (OneView).
- Inter-switch traffic on the same EPON (laser) does not increment traffic counters on bandwidth page (Spectra Only).
- Sometimes after a new Edge Switch is added, some or all of its ports may not be immediately visible on the 'Ports' page.
Workaround: Refresh the browser.
Comments
0 comments
Please sign in to leave a comment.