There’s too much threshold in the Change of Value (COV).
For example, when the lights turn on, there’s a response back saying the lights turned on. Or, the temperature fluctuates by a certain amount, and a notification gets sent.
Have to send back that you received the Change of Value.
It’s a configuration issue that can create a lot of traffic.
Why it fails
Configuration issue, where the value has increments that are too small. E.g. Change of Value should be 2° instead of 0.001°.
Leftover commissioning trend logs.
Getting Confirmed-COVs for irrelevant changes. E.g. a confirmation on temperature, or lighting. Usually you want a Confirmed COV with outputs, not inputs.
How to fix it
Find the device that’s sending out too many COVs, and reconfigure the device.